Product Model Meaning
10kV SF6 fully insulated, fully enclosed, compact ring network switchgear
The HQC-12 type SF6 fully insulated fully enclosed compact ring network
key word:
rated
temperature
environmental
Category:
Intelligent High-Voltage Series

Hotline:
10kV SF6 fully insulated, fully enclosed, compact ring network switchgear
Text and image details
The HQC-12 type SF6 fully insulated, fully enclosed, compact ring network switchgear adopts a modular design, perfectly unifying fixed and flexible expansion to suit the requirements of end users or network nodes, while meeting the needs of various power distribution switchgears, ring network cabinets, and cable branch boxes.
This product uses an SF6 load switch, with a spring-energy storage operating mechanism and a quick-make, quick-break device. The tripping mechanism automatically stretches the spring to store energy during the closing operation, and is controlled by a tripping coil or HRC fuse to release the latch. The gas tank is made of stainless steel, using laser welding, completely sealed, with no leaks, and requires no sealing rings.
This product features a compact structure, safety and reliability, small footprint, long service life, and maintenance-free operation.

Main Technical Parameters
Rated Voltage | 12kV | |
Rated Frequency | 50Hz | |
Number of Phases | Three-phase | |
Rated Current | 630A | |
Insulation Level | 1min Power Frequency Withstand Voltage (RMS) | Power frequency withstand voltage: 42kV (phase-to-phase and phase-to-ground), 48kV (isolation gap) |
Lightning Impulse Withstand Voltage (Peak) | ||
Rated Short-Time Withstand Current | 25kA s | |
Rated Peak Withstand Current | 63kA | |
Operating Mechanism | Rated voltage: AC220/110V or DC220/110V, AC220V is preferred | |
Rated Active Load Breaking Current/Number of Operations | 630A/200 times | |
Electrical Life | E3 level | |
Mechanical Life | Main switch: ≥5000 times | |
Transfer Current of Combination Electric Apparatus | ≥1400A | |
Annual Leakage Rate | ≤0.1% | |
Internal Arc | 25kA/0.5s | |
Gas Tank/Enclosure Protection Level | ≥IP67/IP41 |
Operating Environmental Conditions
● Normal Environmental Conditions
The HQC-12 ring network cabinet generally operates/serves under normal conditions, conforming to DL/T593-1996. The specific limits are as follows:
Ambient Temperature | Temperature | Maximum Average Relative Humidity |
Highest Temperature | +60℃ | 24-hour measurement ≤95% |
Lowest Temperature | -40℃ | 1-month measurement ≤95% |
Without reducing the gas pressure during installation: | ||
Maximum Altitude | 4000m |
|
● Special Environmental Conditions
For special harsh operating environments that differ from normal environmental conditions, users must consult the manufacturer in advance.
For example: When electrical equipment is installed at an altitude of more than 4000m, the atmospheric pressure will decrease, and therefore, overpressure in the cabinet must also be eliminated.